Duct wrap vs. duct board
Most duct insulation is either flexible fiberglass wrap or rigid fiberglass board. The specification usually decides which goes where, but the two are estimated differently, and mixing them up changes the square feet, the accessories and the labor.
Duct wrap
- Flexible blanket, usually with a foil-scrim-kraft (FSK) vapor retarder facing.
- Common densities of 3/4, 1 and 1-1/2 lb per cubic foot, in thicknesses from 1-1/2 to 3 inches.
- Used on concealed duct: above ceilings and in shafts.
- Sold by the roll; thicker wrap means fewer square feet per roll.
- Its installed R-value is lower than its labeled thickness suggests, because wrap is compressed at the corners. Manufacturers publish installed R-values that assume about 25 percent compression.
Duct board
- Rigid fiberglass board, commonly 3 or 6 lb density, 1 to 3 inches thick, with FSK or an all-service jacket (ASJ).
- Used where the duct is exposed and where it has to take abuse or a finish, and on outdoor duct under a weather jacket.
- Sold by the box of sheets.
Square feet: the difference that matters
Both start from the duct's outside perimeter × length. Board adds four times its thickness to the perimeter, because two faces are boarded first and the other two lap over them. On a 24 × 12 duct with 2 inch board, that's 6.67 feet of perimeter per foot of duct instead of 6. The duct calculator shows both.
Pins and tape
Board is pinned on all faces on close centers; outdoor wrap is pinned on every face under its jacket; indoor wrap is usually pinned only on the bottom of wide duct. Joints are sealed with foil tape. Count pins and tape at your own spacing and coverage; NAIMA publishes installation guidance for fastener spacing.
Outdoors
Outdoor duct usually takes board under a weather jacket, either aluminum or a self-adhering membrane jacket, applied over the board's area plus laps and waste. The specification names the jacket.
Lined duct
Internally lined duct has its insulation inside, installed by the sheet metal contractor. It's not part of the insulation scope unless the specification asks for exterior insulation on it as well.