Pipe insulation square feet and jacket calculator
Aluminum, PVC and other jackets are bought by the square foot of insulation surface they cover. Pick the pipe, the insulation wall and the length to get the jacket square feet and the number of 3 foot sections of pipe covering.
The math
- Insulated OD = pipe outside diameter + 2 × insulation wall.
- Surface per foot = π × insulated OD ÷ 12 (square feet per linear foot).
- Jacket = surface per foot × length, plus your allowance for laps and waste.
- Sections: fiberglass pipe covering comes in 3 foot sections, so length ÷ 3, rounded up.
Outside diameters are the standard ones: steel pipe per ASME B36.10 (2 inch is 2.375 inch OD), and copper tube at its nominal size plus 1/8 inch (2 inch copper is 2.125 inch OD). Using the nominal size instead understates the jacket on small pipe.
Example: 100 ft of 1 inch copper at a 1 inch wall
Copper OD 1.125 inch, insulated OD 3.125 inch, surface π × 3.125 ÷ 12 = 0.818 sq ft per foot, so 81.8 sq ft of jacket before waste and 34 sections of pipe covering.
Questions
Does the jacket cover the fittings too?
No. Fittings take preformed PVC fitting covers, counted per fitting. See the fitting cover size chart.
How much should I add for laps?
Jacket laps on the longitudinal seam and at the circumferential joints. Many estimators carry 10 to 15 percent for laps and waste; use what your crews actually see.
Copper or iron size for the insulation?
Insulation fits the pipe's outside diameter. Copper is ordered by copper tube sizes (a 2 inch copper line takes 2-1/8 inch covering), iron pipe by its own pipe size.