Pipe insulation thickness by service and pipe size
The thickness on each line of a pipe insulation takeoff usually comes from one of three places. In order of authority they are the project specification, the energy code table the specification points to, and your own house standard when neither says anything. This guide covers the code table that most specifications copy, and how to apply it.
Where the numbers come from
Commercial projects in most of the US fall under ASHRAE Standard 90.1 or the commercial provisions of the International Energy Conservation Code (IECC). Both set a minimum pipe insulation thickness by fluid temperature and nominal pipe size. Division 22 and 23 insulation sections (22 07 19, 23 07 19) often reprint that table, sometimes with thicker values. When the specification gives its own table, use the specification.
Minimum thickness, inches
Values for insulation with a conductivity in the code's reference range (typical fiberglass and elastomeric). Check the edition your jurisdiction has adopted; the table has changed between editions.
| Service | Fluid temperature | < 1" | 1" to < 1-1/2" | 1-1/2" to < 4" | 4" to < 8" | 8" and up |
|---|---|---|---|---|---|---|
| Steam, high pressure | Above 350 °F | 4.5 | 5.0 | 5.0 | 5.0 | 5.0 |
| Steam, medium pressure | 251 to 350 °F | 3.0 | 4.0 | 4.5 | 4.5 | 4.5 |
| Steam, low pressure | 201 to 250 °F | 2.5 | 2.5 | 2.5 | 3.0 | 3.0 |
| Heating hot water | 141 to 200 °F | 1.5 | 1.5 | 2.0 | 2.0 | 2.0 |
| Domestic hot water, low-temp heating | 105 to 140 °F | 1.0 | 1.0 | 1.5 | 1.5 | 1.5 |
| Chilled water, condensate | 40 to 60 °F | 0.5 | 0.5 | 1.0 | 1.0 | 1.0 |
| Brine, refrigerant | Below 40 °F | 1.0 | 1.0 | 1.5 | 1.5 | 1.5 |
Applying it on a takeoff
- Read the service, then the size. The same 2" pipe is 1-1/2" thick on domestic hot water and 2" on heating hot water. Thickness can change at a size break along one run, so carry it per size.
- Cold water and storm. The energy table doesn't cover domestic cold water or storm leaders; specifications usually call for 1/2" or 1" against condensation. If the specification is silent, that's a house-standard decision.
- Hot water return takes the same thickness as the hot water it returns.
- Refrigerant line sets are usually elastomeric, often 1/2" on liquid lines and 3/4" or 1" on suction lines; equipment manufacturers' instructions can require more.
- Outdoors and underground the specification often adds thickness and a jacket. Read those paragraphs separately; see reading insulation specs.
Why thickness matters to the price
Thicker insulation costs more per foot. It also changes the outside diameter, which changes jacket square feet and fitting cover sizes. On large pipe, 2" and up of fiberglass may need two layers. Price thickness per line rather than averaging it across a job. The pipe insulation jacket calculator shows the jacket area for a given pipe size and thickness.
Questions
Does the specification or the energy code win?
The specification, when it is at least as thick as the code. A specification can't go below the code that applies, but it can and often does require more.
Is domestic cold water required to be insulated?
Not by the energy code table. It's insulated against condensation when the specification calls for it, usually at 1/2" or 1".
Do the values change for other insulation materials?
Yes. The table assumes a reference conductivity. A material that insulates less well per inch needs more thickness, and the code gives a formula for the adjustment.